Strona 1 - EtherNet/IP

EtherNet/IPIAI America Inc. Operation Manual, Fourth EditionACON-C/CGPCON-C/CG/CA/CFASCON-CA

Strona 2

2No.Operation Description Description 2 Transportation Ɣ When carrying a heavy object, do the work with two or more persons or utilize equipment su

Strona 3 - Please Read Before Use

3. SCON-CA/CFA923.5.4 Setting the Subnet Mask Set parameter No. 141, “SNMK: Subnet mask.” Set the same value you have set in the master unit and

Strona 4

3. SCON-CA/CFA933.6 Communicating with the Master Station 3.6.1 Operation Modes and Corresponding PLC I/O Areas The addresses allocated for each ope

Strona 5 - Table of Contents

3. SCON-CA/CFA94x PCON-CA/CFA outputoPLC input side (* “n” indicates the first input address of each axis.) DO on the PCON-CA/CFA side and output dat

Strona 6

3. SCON-CA/CFA953.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) In this operation method, EtherNet/IP communications is used to mimic the operati

Strona 7

3. SCON-CA/CFA96(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84PCON-CA/CFA side DI (Port No.) PLC sid

Strona 8

3. SCON-CA/CFA97(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to operation

Strona 9 - Safety Guide

3. SCON-CA/CFA98Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category Port No. Symbol Si

Strona 10

3. SCON-CA/CFA993.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) In this operation mode, EtherNet/IP communication is used t

Strona 11

3. SCON-CA/CFA100(2) I/O signal allocation for each axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and four output

Strona 12

3. SCON-CA/CFA101PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strona 13

3No.Operation Description Description (2) Cable Wiring Ɣ Use our company’s genuine cables for connecting between the actuator and controller, and for

Strona 14

3. SCON-CA/CFA102(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strona 15 - Alert Indication

3. SCON-CA/CFA103(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Current pos

Strona 16 - Handling Precautions

3. SCON-CA/CFA1043.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning band, s

Strona 17 - 1. Overview

3. SCON-CA/CFA105(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output w

Strona 18 - 1. Overview

3. SCON-CA/CFA106PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negative figu

Strona 19 - 2. ACON-C/CG, PCON-C/CG

3. SCON-CA/CFA107PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strona 20 - 2. ACON-C/CG, PCON-C/CG

3. SCON-CA/CFA108(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strona 21

3. SCON-CA/CFA109(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsPressing cur

Strona 22 - 2.2 Model Numbers

3. SCON-CA/CFA110(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Current pos

Strona 23 - /5 .'&

3. SCON-CA/CFA1113.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position, speed,

Strona 24

4No.Operation Description Description 4 Installation and Start(4) Safety Measures Ɣ When the work is carried out with 2 or more persons, make it cle

Strona 25 - 2.4.1 Connection Diagram

3. SCON-CA/CFA112(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one output

Strona 26 - 2.5.2 Setting the Baud Rate

3. SCON-CA/CFA113PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negative figu

Strona 27

3. SCON-CA/CFA114Address (* “n” indicates the first output address of each axis.) When the zone boundary is shown using the negative figure, it is exp

Strona 28

3. SCON-CA/CFA115PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strona 29

3. SCON-CA/CFA116Address (* “n” indicates the first input address of each axis.) 1 word = 2 bytes = 16 bits n+20, n+21 b15 b14 b13 b12 b11 b10

Strona 30

3. SCON-CA/CFA117(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strona 31

3. SCON-CA/CFA118(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function DetailsAcceleration 16-

Strona 32 - ACON

3. SCON-CA/CFA119(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function Detailsb2 DIR Pressing

Strona 33

3. SCON-CA/CFA120(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsCurrentposit

Strona 34 - PCON

3. SCON-CA/CFA121(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Detailsb15 EMGS Em

Strona 35

5No.Operation Description Description 6 Trial Operation Ɣ When the work is carried out with 2 or more persons, make it clear who is to be the leade

Strona 36

3. SCON-CA/CFA1223.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) In this operation method, EtherNet/IP communications is used to mimic the ope

Strona 37

3. SCON-CA/CFA123(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84PCON-CA/CFA side DI and input regis

Strona 38

3. SCON-CA/CFA124PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strona 39

3. SCON-CA/CFA125(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the

Strona 40

3. SCON-CA/CFA1263.6.7 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bit signal

Strona 41

3. SCON-CA/CFA127(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turned ON, t

Strona 42

3. SCON-CA/CFA128(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under home return operation (GHMS) PLC

Strona 43

3. SCON-CA/CFA129(7) Positioning start (CSTR): Used in the position/simple direct mode PLC output signal This signal is processed at the startup (ON

Strona 44

3. SCON-CA/CFA130TravelSpeedPositioning band TimeTarget position Timing at which the position complete signal turns ON (10) Positioning completion sig

Strona 45

3. SCON-CA/CFA131Zone signal+ direction Actuator operation Home Zone setting -Zone setting +(12) Zone 1 (ZONE1) PLC input signal Zone 2 (ZONE2)

Strona 46

6No.Operation Description Description 8 Maintenance and Inspection Ɣ When the work is carried out with 2 or more persons, make it clear who is to be

Strona 47

3. SCON-CA/CFA132(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup or inch

Strona 48

3. SCON-CA/CFA133(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifying the jo

Strona 49

3. SCON-CA/CFA134(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is turned

Strona 50

3. SCON-CA/CFA135SpeedTravelPositioning band Positioning band Positioning band DIR = OFF Target position DIR = ON (19) Operating mode selector (RMOD)

Strona 51

3. SCON-CA/CFA136(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator moved the

Strona 52

3. SCON-CA/CFA137(26) Load output judgment (LOAD) PLC input signal This signal is available only in the pressing operation. When this signal is used f

Strona 53

3. SCON-CA/CFA138Target positionTravelSpeedPosition where the actuator is pushed against the work part and the pressing completion is judged so the po

Strona 54

3. SCON-CA/CFA139(28) Stopping control mode (SMOD) PLC output signal One of the pulse motor general characteristics is that that the holding curren

Strona 55

3. SCON-CA/CFA140Setting: 50 Setting: 100Setting: 10 (29) Acceleration/deceleration mode (MOD1ޔMOD0) PLC output signal This signal is used to select t

Strona 56

3. SCON-CA/CFA141Caution: [1] Even if a position command or direct value command with S-shaped motion setting is issued when the actuator is running,

Strona 57

7Alert Indication The safety precautions are divided into “Danger”, “Warning”, “Caution” and “Notice” according to the warning level, as follows, and

Strona 58

3. SCON-CA/CFA142(30) Stop Mode Selection (ASO1, ASO0) PLC Output Signal Select the stop mode for the duration before the movement to the next posi

Strona 59

3. SCON-CA/CFA143PLC sequence programControl signalStatus signalPCON Control signalStatus signalMaster station o Slave transmission de

Strona 60

3. SCON-CA/CFA1443.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode, Half direct value mode and

Strona 61

3. SCON-CA/CFA145* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3 (msec) [7][1][2][3][

Strona 62

3. SCON-CA/CFA146(2) Operation in the half direction mode It is operated with the data set in the PLC's target position register, positioning ba

Strona 63

3. SCON-CA/CFA147*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Positioning band

Strona 64

3. SCON-CA/CFA148(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as the tar

Strona 65

3. SCON-CA/CFA149[1][2][3][4][5][6][7][8]Set value of target position data Set value of positioning band data Set value of speed data Set value of pos

Strona 66

3. SCON-CA/CFA150*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3 (msec) [9][10][11][12]

Strona 67

3. SCON-CA/CFA151[1][2][3]Actuator speed Speed n2 Speed n3 Set value of speed or acceleration/deceleration (4) Data change during movement In the hal

Strona 68

8Handling Precautions 1. It is recommended that the baud rate be set based on auto negotiation. Make sure the link setting of the EtherNet/IP unit m

Strona 69

3. SCON-CA/CFA1523.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84, No. 86 to 87, No. 90, No. 140 to 142 and No. 159.

Strona 70

3. SCON-CA/CFA153z Network type (No.87 NTYP) The network module type is set for the parameter No. 87. Do not change the default value. z Field I/O f

Strona 71

3. SCON-CA/CFA154(Example ii) Set value = “1” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecima

Strona 72

3. SCON-CA/CFA155(Example iii) Set value = “2” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecim

Strona 73

3. SCON-CA/CFA156(Example iv) Set value = “3” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecima

Strona 74

3. SCON-CA/CFA157z IP address (No. 140: IPAD) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Factory set

Strona 75

4. SCON-CA1584. SCON-CA 4.1 Operation Modes and Functions SCON-CA controllers supporting Ethernet/IP can be operated in a desired operation mode sel

Strona 76

4. SCON-CA159[2] Position/simple direct mode: In this mode, the actuator is operated by specifying position numbers. You can select whether to specif

Strona 77

4. SCON-CA160[4] Full direct mode: In this mode, the actuator is operated by specifying all values relating to position control (target position, spe

Strona 78 - 2.7 I/O Signal Timings

4. SCON-CA161[7] Half direct mode 2: In this mode, the actuator is operated by specifying the speed, acceleration/deceleration and pressing current,

Strona 79 - 2.8 Operation

1. Overview91. Overview EtherNet/IP is an open field network. It is a standardized global open network specified by the IEC 61158 series of internati

Strona 80

4. SCON-CA1624.2 Model Numbers The model numbers of SCON-CA controller supporting EtherNet/IP are indicated as follows, respectively: z SCON-CA--EP

Strona 81

4. SCON-CA1634.3 EtherNet/IP Interface 4.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follows. NS LEDEth

Strona 82

4. SCON-CA1644.3.2 Monitor LED Indications The slave condition (each controller), as well as network condition, can be checked using the two LEDs, MS

Strona 83

4. SCON-CA1654.4 Wiring 4.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminum tape and braided doub

Strona 84

4. SCON-CA1664.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the controller to “MANU

Strona 85

4. SCON-CA1674.5.3 Setting the IP Address Set parameter No. 140, “IPAD: IP address.” [Refer to 4.9, “EtherNet/IP Parameters.”] Settable Range:0

Strona 86

4. SCON-CA1684.6 Communicating with the Master Station 4.6.1 Operation Modes and Corresponding PLC I/O Areas The channels allocated for each operati

Strona 87

4. SCON-CA169x PLC output o SCON-CA input side (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Posit

Strona 88

4. SCON-CA170x SCON-CA output o PLC input (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Remote I/O

Strona 89

4. SCON-CA171x SCON-CA outputoPLC input Side (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Positio

Strona 90

1. Overview101.1 EtherNet/IP Specifications Item Specification Communication standards IEC61158 (IEEE802.3) Baud rate 10BASE-T/100 BASE-T (Auto n

Strona 91

4. SCON-CA1724.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) This is the operation mode with the position No. set up as the same as using PIO (24

Strona 92 - 2.10 Troubleshooting

4. SCON-CA173(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No.84SCON-CA side DI(Port No.) PLC side output

Strona 93 - 3. PCON-CA/CFA

4. SCON-CA174(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to Operation Ma

Strona 94

4. SCON-CA175Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category Port No. Symbol Sig

Strona 95

4. SCON-CA176Setting of parameter No. 25 Force control mode 1 Force control mode 2 6 7 Category Port No. Symbol Signal name Symbol Signal name 0

Strona 96 - 3.2 Model Numbers

4. SCON-CA1774.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) This is the operation mode with the position No. set up. Wheth

Strona 97 - 3.3.1 Names of the Parts

4. SCON-CA178 (2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and four output wo

Strona 98 - 3.4.1 Connection Diagram

4. SCON-CA179PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 99 - 3.5.2 Setting the Baud Rate

4. SCON-CA180(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal Type Bit Symbol Conten

Strona 100 - 3. SCON-CA/CFA

4. SCON-CA181(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal Type Bit Symbol Contents Details Current positio

Strona 101

2. ACON-C/CG, PCON-C/CG112. ACON-C/CG, PCON-C/CG 2.1 Operation Modes and Functions ACON and PCON controllers equipped with EtherNet/IP can be operat

Strona 102

4. SCON-CA1824.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning band, speed

Strona 103

4. SCON-CA183(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strona 104

4. SCON-CA184PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strona 105 - (3) I/O signal assignment

4. SCON-CA185PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 106

4. SCON-CA186(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Conten

Strona 107

4. SCON-CA187(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Pressingcurrent

Strona 108

4. SCON-CA188(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strona 109

4. SCON-CA1894.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position, speed, etc.

Strona 110

4. SCON-CA190(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one output word

Strona 111

4. SCON-CA191PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strona 113

2. ACON-C/CG, PCON-C/CG12[2] Position/simplified direct value mode: In this operation mode, EtherNet/IP communication is used to select and command

Strona 114

4. SCON-CA192Address (* “n” indicates the node address of each axis.) When the zone boundary is shown using the negative figure, it is expressed using

Strona 115

4. SCON-CA193PLC input Channel (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 116

4. SCON-CA194 b15n+18, n+19 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b032,768 16,384 8,192 4,096 2,048 1,024 512 256 128 64 32 16 8 4 2 1b15 b14

Strona 117

4. SCON-CA195(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Conten

Strona 118

4. SCON-CA196(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Address Bit Symbol

Strona 119

4. SCON-CA197(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Address Bit Symbol

Strona 120

4. SCON-CA198(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Signal type Bit Symb

Strona 121

4. SCON-CA199(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Signal type Bit Symb

Strona 122

4. SCON-CA2004.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) This is the operation mode with the position No. set up as the same as using PIO

Strona 123

4. SCON-CA201(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No. 84 SCON-CA side DI and input register PLC

Strona 124

2. ACON-C/CG, PCON-C/CG13[4] Full direct value mode: In this operation mode, all values regarding position control (“Target Position,” "Speed”

Strona 125

4. SCON-CA202PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 126

4. SCON-CA203(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the remo

Strona 127

4. SCON-CA2044.6.7 Position/Simplified Direct Value Mode2 (Number of Occupied Bytes: 8) In this mode, the actuator is operated by means of force con

Strona 128

4. SCON-CA205(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (4 words = 8 bytes) and one output word i

Strona 129

4. SCON-CA206PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 130

4. SCON-CA207(3) I/O signal assignments(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is

Strona 131

4. SCON-CA208(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strona 132

4. SCON-CA2094.6.8 Half Direct Value Mode 2 (Number of Occupied Bytes: 16) In this mode, the actuator is operated by means of force control (pressing

Strona 133

4. SCON-CA210(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strona 134

4. SCON-CA211PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strona 135

2. ACON-C/CG, PCON-C/CG142.2 Model Numbers The Model numbers of ACON and PCON applicable to EtherNet/IP are described as follows. Ɣ ACON-C/CG--EP-

Strona 136

4. SCON-CA212PLC input Address (* “n” indicates the node address of each axis.) When the current position is a negative figure, it is expressed using

Strona 137

4. SCON-CA213(3) I/O signal assignment(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Content

Strona 138

4. SCON-CA214(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Pressing current

Strona 139

4. SCON-CA215(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strona 140

4. SCON-CA2164.6.9 Remote I/O Mode 3 (Number of Occupied Bytes: 12) In this mode, force control (feedback pressing of load cell values) is used in ad

Strona 141

4. SCON-CA217(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No. 84 SCON-CA side DI and input register PLC

Strona 142

4. SCON-CA218PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 143

4. SCON-CA219(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the remo

Strona 144

4. SCON-CA2204.6.10 Half Direct Value Mode 3 (Number of Occupied Bytes: 16) In this mode, the jog function in the half direct numerical mode is not a

Strona 145

4. SCON-CA221(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strona 146

2. ACON-C/CG, PCON-C/CG152.3 EtherNet/IP Interface 2.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follow

Strona 147

4. SCON-CA222PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strona 148

4. SCON-CA223PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strona 149

4. SCON-CA224(3) I/O signal assignment(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Content

Strona 150 - Function

4. SCON-CA225(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Description Details Pressingcurr

Strona 151 - 3.7 I/O Signal Timings

4. SCON-CA226(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strona 152 - 3.8 Operation

4. SCON-CA2274.6.11 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bit signal i

Strona 153

4. SCON-CA228(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turned ON, the s

Strona 154

4. SCON-CA229(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under Home return Operation (GHMS) PLC inpu

Strona 155 - Pressing

4. SCON-CA230(7) Positioning start (CSTR):Used in the position/simple direct mode PLC output signal This signal is processed at the startup (ON ed

Strona 156

4. SCON-CA231(10) Positioning completion signal (PEND) PLC input signal This signal is turned “ON” when the actuator is moved to the target posit

Strona 157

2. ACON-C/CG, PCON-C/CG162.3.2 Monitor LED Indications The slave condition (each controller), as well as network condition, can be checked using the

Strona 158

4. SCON-CA232(12) Zone 1 (ZONE1) PLC input signal Zone 2 (ZONE2) PLC input signal Position zone (PZONE) PLC input signal These signals are turned O

Strona 159

4. SCON-CA233(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup or inching op

Strona 160

4. SCON-CA234(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifying the jo

Strona 161

4. SCON-CA235(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is turned “ON”

Strona 162

4. SCON-CA236(19) Operating mode selector (RMOD) PLC output signal Operation Mode Status (RMDS) PLC input signal The operation mode is selecte

Strona 163

4. SCON-CA237(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator moved the t

Strona 164

4. SCON-CA238(26) Load output judgment (LOAD) PLC input signal This signal is available only in the pressing operation. When this signal is used fo

Strona 165 - 3.10 Troubleshooting

4. SCON-CA239(27) Torque level (TRQS) PLC input signal This signal is available only in the pressing operation. When the motor current reaches th

Strona 166 - Communication

4. SCON-CA240(28) Absolute battery voltage low 2arning (BALM) PLC input signal With an absolute system, this signal is OFF when the absolute battery

Strona 167

4. SCON-CA241(30) Acceleration/deceleration mode (MOD1, MOD0) PLC output signal This signal is used to select the acceleration/deceleration pattern

Strona 168 - Position No. 0

2. ACON-C/CG, PCON-C/CG17812.4 Wiring Example 2.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminu

Strona 169

4. SCON-CA242First-Order Lag Filter This describes much gentle acceleration/deceleration curve than that for the linear acceleration/deceleration (t

Strona 170 - 4.2 Model Numbers

4. SCON-CA243(31) Standstill mode selection (ASO0, ASO1) PLC output signals Select the stop mode to be applied while the actuator is standing by to

Strona 171 - 4.3.1 Names of the Parts

4. SCON-CA244(32) Load cell calibration command (CLBR) PLC output signal Load cell calibration complete (CEND) PLC input signal The factory settin

Strona 172 - 4. SCON-CA

4. SCON-CA2454.7 I/O Signal Timings When any of the control signal is turned ON to perform the operation of the actuator using the PLC's sequenc

Strona 173 - 4.4.1 Connection Diagram

4. SCON-CA2464.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode 1 and 2 , Half Direct Value Mode

Strona 174 - 4.5.2 Setting the Baud Rate

4. SCON-CA247*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) [1][2]Set value of ta

Strona 175

4. SCON-CA248(2) Operation in the half direction mode 1 to 3 It is operated with the data set in the PLC's target position register, positioning

Strona 176

4. SCON-CA249*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Set value of target p

Strona 177

4. SCON-CA250(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as the target

Strona 178

4. SCON-CA251Set value of target position data [1][2]Set value of positioning band data Set value of speed data [3][4][5][6][7][8]Set value of positio

Strona 179

2. ACON-C/CG, PCON-C/CG182.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the control

Strona 180

4. SCON-CA252* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3(msec) [9]Positioning ban

Strona 181

4. SCON-CA253(4) Data change during movement In the half direct mode or full direct mode 1 to 3, the value currently set to a given resister among th

Strona 182

4. SCON-CA2544.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84 to No. 87, No. 90, No. 140 to No. 142 and No.159. .Cate

Strona 183

4. SCON-CA255z Fieldbus baud rate (No. 86: FBRS) Specify the baud rate in parameter No. 86. Set value Baud rate 0 (Factory setting) Auto negotia

Strona 184

4. SCON-CA256z Field I/O format (No.90 FMIO) Addresses in the PLC are assigned in units of 16 points (2 bytes) based on the node address set in the co

Strona 185

4. SCON-CA257(Example ii) Set value = “1” z indicates ON, while c indicates OFF SCON Inputresister SCON OutputresisterHexadecimal dataPLC:OutputCHPLC

Strona 186

4. SCON-CA258(Example iii) Set value = “2” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadecimal dataPLC

Strona 187

4. SCON-CA259(Example iv) Set value = “3” z indicates ON, while c indicates OFF SCON Inputresister SCON Outputresister Hexadecimal dataPLC:OutputCHPL

Strona 188

4. SCON-CA260z IP address (No. 140: NADR) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Factory setting:

Strona 189

4. SCON-CA2614.10 Troubleshooting z Alarm messages and causes/actions When an alarm occurs, a corresponding simple alarm code is indicated by the

Strona 190

2. ACON-C/CG, PCON-C/CG192.5.4 Setting the Subnet Mask Set parameter No. 141, “SNMK: Subnet mask.” Set the same value you have set in the master

Strona 191

5. Appendix262OMRONPLCIAI RC controller Switching hubLAN cable LAN cable 5. Appendix Examples of connection settings with Omron’s master and Keyenc

Strona 192

5. Appendix2635.1.3 Setting the PLC (1) [CX-Programmer] [1] Set “NODE No.” rotary switches “x161” and “x160” to “0” and “A,” respectively, on the

Strona 193

5. Appendix264[6] In the “PLC I/O Table” window, double-click “Built-in Ports/Inner Boards” and then double-click “[1500] CJ2M-EIP21.” [7] In the “C

Strona 194

5. Appendix2655.1.4 Setting the PLC (2) [Network Configurator] [1] Start Network Configurator and click the [Connect] button on the toolbar to con

Strona 195

5. Appendix266[4] Right-click each device in the main window and select [Change Node Address] in the pop-up menu to set the IP address.

Strona 196

5. Appendix267PLC’s IP Address Controller’s IP Address

Strona 197

5. Appendix268[5] Double-click “Anybus-CC EtherNet/IP” in the main window and set the controller device parameters as follows: Item Set value 0001

Strona 198

5. Appendix269[7] Once the device is registered, “Anybus-CC EtherNet/IP” moves to “List of Registered Devices.” Double-click “Anybus-CC EtherNet/IP”

Strona 199

5. Appendix270[8] In the “Assign Connection” dialog box, click the [Edit Tag Set] button next to “Input Tag Set” in the Originator Device area.

Strona 200

5. Appendix271[9] In the “Edit Tag Set” dialog box, click the [Edit Tag] button. [10] In the “Edit Tag” dialog box, click the [New] button.

Strona 201

2. ACON-C/CG, PCON-C/CG202.6 Communicating with the Master Station 2.6.1 Operation Modes and Corresponding PLC I/O Areas The addresses allocated for

Strona 202

5. Appendix272[11] In the “Set Tag” dialog box, set as follows and click the [Register] button. [12] When tag “W0’” has been registered in the “Se

Strona 203

5. Appendix273[14] In the “Assign Connection” dialog box, set as follows and click the [Register] button. Confirm that the values in the “Target De

Strona 204

5. Appendix274[17] Upon establishment of link, the LEDs on the PLC and controller change their statuses as follows: LED statuses on PLC LED status

Strona 205

5. Appendix2755.1.5 Checking the I/O Data on the PLC [1] Start CX-Programmer. [2] Click the [Switch Watch Window] button on the toolbar. [3]

Strona 206

5. Appendix276PLCIAI RC controller Switching hubLAN cable LAN cable 5.2 Example of Connection Settings with Keyence’s Master The following devices

Strona 207

5. Appendix2775.2.3 Setting the PLC [1] Start Keyence’s ladder support software “KV-STUDIO.” [2] Start the Unit Editor and set the baud rate, IP

Strona 208

5. Appendix278[4] When the device is registered in the tree below the PLC, the “Default Adapter Settings” dialog box appears. Set the IP address and

Strona 209

5. Appendix279[6] In the “Set Connection” dialog box, set the connection type and send trigger. Select “Point-to-Point” for the connection type for b

Strona 210

5. Appendix280[8] Click the “Assign Device” button in the “Set Connection” dialog box to open the “Set Devices” dialog box. In this dialog box, set t

Strona 211

5. Appendix281[10] Click the “Apply” button in the bottom right-hand corner of the “Unit Editor” to update the EtherNet/IP setting information. Next,

Strona 212

2. ACON-C/CG, PCON-C/CG21x ACON/PCON outputoPLC input side (* “n” indicates the first input address of each axis.) DO on the ACON or PCON side and ou

Strona 213

5. Appendix2825.2.4 Checking the I/O Data on the PLC [1] Start KV-STUDIO in the “Monitor Mode.” [2] In the “Workspace” window, right-click “Anybu

Strona 214

Change History283Change History Revision date Description of revision February 2011 November 2011 June 2012 November 2012 First edition Second edit

Strona 217

Manual No.: ME0278-4B (November 2012)The information contained in this document is subject to change without notice for purposes ofproduct improvement

Strona 218

Please Read Before Use Thank you for purchasing our product. This operation manual explains the handling methods, structure and maintenance of this pr

Strona 219

2. ACON-C/CG, PCON-C/CG222.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) In this operation method, EtherNet/IP communications is used to mimic th

Strona 220

2. ACON-C/CG, PCON-C/CG23(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84ACON/PCON side DI (Port No.

Strona 221

2. ACON-C/CG, PCON-C/CG24(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to

Strona 222

2. ACON-C/CG, PCON-C/CG25 ACON Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category

Strona 223

2. ACON-C/CG, PCON-C/CG26 PCON Parameter No. 25 setting Positioning mode Teaching mode 256-point mode 0 1 2 Category PortNo.Symbol Signal name

Strona 224

2. ACON-C/CG, PCON-C/CG27 PCON Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category P

Strona 225

2. ACON-C/CG, PCON-C/CG282.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) In this operation mode, EtherNet/IP communication

Strona 226

2. ACON-C/CG, PCON-C/CG29(2) I/O signal allocation for each axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and fou

Strona 227

2. ACON-C/CG, PCON-C/CG30PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strona 228

2. ACON-C/CG, PCON-C/CG31(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strona 230

2. ACON-C/CG, PCON-C/CG32(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Cur

Strona 231

2. ACON-C/CG, PCON-C/CG332.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning

Strona 232

2. ACON-C/CG, PCON-C/CG34(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one

Strona 233

2. ACON-C/CG, PCON-C/CG35PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negat

Strona 234

2. ACON-C/CG, PCON-C/CG36PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strona 235

2. ACON-C/CG, PCON-C/CG37(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strona 236

2. ACON-C/CG, PCON-C/CG38(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsPres

Strona 237

2. ACON-C/CG, PCON-C/CG39(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Cur

Strona 238

2. ACON-C/CG, PCON-C/CG402.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position,

Strona 239

2. ACON-C/CG, PCON-C/CG41(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one

Strona 240

Table of Contents Safety Guide...

Strona 241

2. ACON-C/CG, PCON-C/CG42PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negat

Strona 242

2. ACON-C/CG, PCON-C/CG43Address (* “n” indicates the first output address of each axis.) When the zone boundary is shown using the negative figure, i

Strona 243

2. ACON-C/CG, PCON-C/CG44PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strona 244

2. ACON-C/CG, PCON-C/CG45(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strona 245

2. ACON-C/CG, PCON-C/CG46(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function DetailsAccelera

Strona 246

2. ACON-C/CG, PCON-C/CG47(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function Detailsb5b4-Una

Strona 247

2. ACON-C/CG, PCON-C/CG48(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsCurr

Strona 248

2. ACON-C/CG, PCON-C/CG492.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) In this operation method, EtherNet/IP communications is used to mimic

Strona 249

2. ACON-C/CG, PCON-C/CG50(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84ACON/PCON side DI and input

Strona 250

2. ACON-C/CG, PCON-C/CG51PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strona 251

3.6 Communicating with the Master Station...933.6.1 Operation Modes

Strona 252

2. ACON-C/CG, PCON-C/CG52(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments

Strona 253 - 4.7 I/O Signal Timings

2. ACON-C/CG, PCON-C/CG532.6.7 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bi

Strona 254 - 4.8 Operation

2. ACON-C/CG, PCON-C/CG54(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turn

Strona 255

2. ACON-C/CG, PCON-C/CG55(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under home return operation (GH

Strona 256

2. ACON-C/CG, PCON-C/CG56(7) Positioning start (CSTR): Used in the position/simple direct mode PLC output signal This signal is processed at the star

Strona 257

2. ACON-C/CG, PCON-C/CG57TravelSpeedPositioning band TimeTarget position Timing at which the position complete signal turns ON (10) Positioning comple

Strona 258

2. ACON-C/CG, PCON-C/CG58Zone signal+ direction Actuator operation Home Zone setting -Zone setting +(12) Zone 1 (ZONE1) PLC input signal Zone 2

Strona 259

2. ACON-C/CG, PCON-C/CG59(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup

Strona 260

2. ACON-C/CG, PCON-C/CG60(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifyin

Strona 261 - Speed n3

2. ACON-C/CG, PCON-C/CG61(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is

Strona 262

5.2 Example of Connection Settings with Keyence’s Master ... 2765.2.1 Connection Example ...

Strona 263

2. ACON-C/CG, PCON-C/CG62SpeedTravelPositioning band Positioning band Positioning band DIR = OFF Target position DIR = ON (19) Operating mode selector

Strona 264

2. ACON-C/CG, PCON-C/CG63(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator mo

Strona 265

2. ACON-C/CG, PCON-C/CG64(26) Load output judgment (LOAD) PLC input signal Dedicated PCON function This signal is available only in the pressing opera

Strona 266

2. ACON-C/CG, PCON-C/CG65Target positionTravelSpeedPosition where the actuator is pushed against the work part and the pressing completion is judged s

Strona 267

2. ACON-C/CG, PCON-C/CG66(28) Stopping control mode (SMOD) PLC output signal Dedicated PCON function One of the pulse motor general characteristics

Strona 268

2. ACON-C/CG, PCON-C/CG67Setting: 50 Setting: 100Setting: 10 (29) Acceleration/deceleration mode (MOD1ޔMOD0) PLC output signal Dedicated ACON function

Strona 269 - 4.10 Troubleshooting

2. ACON-C/CG, PCON-C/CG68Caution: [1] Even if a position command or direct value command with S-shaped motion setting is issued when the actuator is

Strona 270 - 5.1.1 Connection Example

2. ACON-C/CG, PCON-C/CG69(30) Stop Mode Selection (ASO1, ASO0) PLC Output Signal Select the stop mode for the duration before the movement to the n

Strona 271 - 5. Appendix

2. ACON-C/CG, PCON-C/CG70PLC sequence programControl signalStatus signalACON, PCONControl signalStatus signalMaster station o Slave transmission

Strona 272

2. ACON-C/CG, PCON-C/CG712.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode, Half direct value m

Strona 274

2. ACON-C/CG, PCON-C/CG72* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3 (msec) [7][1

Strona 275 - Controller’s IP Address

2. ACON-C/CG, PCON-C/CG73(2) Operation in the half direction mode It is operated with the data set in the PLC's target position register, positi

Strona 276

2. ACON-C/CG, PCON-C/CG74*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Position

Strona 277

2. ACON-C/CG, PCON-C/CG75(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as

Strona 278 - Originator Device area

2. ACON-C/CG, PCON-C/CG76[1][2][3][4][5][6][7][8]Set value of target position data Set value of positioning band data Set value of speed data Set valu

Strona 279

2. ACON-C/CG, PCON-C/CG77*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3 (msec) [9][10]

Strona 280

2. ACON-C/CG, PCON-C/CG78[1][2][3]Actuator speed Speed n2 Speed n3 Set value of speed or acceleration/deceleration (4) Data change during movement In

Strona 281

2. ACON-C/CG, PCON-C/CG792.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84, No. 86 to 87, No. 90 and No. 140 to 142. C

Strona 282

2. ACON-C/CG, PCON-C/CG80z Network type (No.87 NTYP) The network module type is set for the parameter No. 87. Do not change the default value. z Fie

Strona 283

2. ACON-C/CG, PCON-C/CG81(Example ii) Set value = “1” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadeci

Strona 284 - 5.2.1 Connection Example

1Safety Guide “Safety Guide” has been written to use the machine safely and so prevent personal injury or property damage beforehand. Make sure to rea

Strona 285 - 5.2.3 Setting the PLC

2. ACON-C/CG, PCON-C/CG82(Example iii) Set value = “2” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadec

Strona 286

2. ACON-C/CG, PCON-C/CG83(Example iv) Set value = “3” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadeci

Strona 287

2. ACON-C/CG, PCON-C/CG84z IP address (No. 140: IPAD) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Fac

Strona 288

3. SCON-CA/CFA853. PCON-CA/CFA 3.1 Operation Modes and Functions PCON-CA/CFA controllers equipped with EtherNet/IP can be operated in the following

Strona 289

3. SCON-CA/CFA86[2] Position/simplified direct value mode: In this operation mode, EtherNet/IP communication is used to select and command movement

Strona 290

3. SCON-CA/CFA87[4] Full direct value mode: In this operation mode, all values regarding position control (“Target Position,” "Speed” and "

Strona 291 - Change History

3. SCON-CA/CFA883.2 Model Numbers The Model numbers of PCON-CA/CFA applicable to EtherNet/IP are described as follows. Ɣ PCON-CA--EP-Ɣ PCON-CFA-

Strona 292

3. SCON-CA/CFA893.3 EtherNet/IP Interface 3.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follows. 3.3.2

Strona 293

3. SCON-CA/CFA90813.4 Wiring Example 3.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminum tape an

Strona 294 - 12.11.000

3. SCON-CA/CFA913.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the controller to “M